docketcity.com
15-9015

FIRE-24-0041 Property Address: 915 DOYLE ROAD, DELTONA, FL 32725 Parcel ID: 910609000010 Property Owner: TCB - DELTONA LLC 353 N CLARK SUITE 3625 CHICAGO, IL 60654-3477 Violation: City of Deltona Ordinance, : Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition, NFPA 13, 2019 Edition – Ch. 16.12.5.6 - Where a fire department connection services only a portion of a building, a sign shall be attached indicating the portions of the building served, NFPA 1 – Ch. 13.3.3.4.3.4 - As-built system installation drawings, hydraulic calculations, original acceptance test records, and device manufacturer’s data sheets shall be retained for the life of the system, Corrective Action: Please contact your fire sprinkler service provider to provide a hydraulic calculation plate for the retail plaza portion of the Publix building. Please provide signage for Fire Department Connection (FDC), directly in front of FDCs for Building 100, 200 & 300. Durable signage shall be a minimum of 6 inches in height, on contrasting background. Please ensure signage indicates "Bldg 100/200/300 FDC" on it. Fire Inspector Ajorie Bailey

Code Violation New Business Introduced August 20, 2024
Committee
Special Magistrate
Introduced
August 20, 2024
On agenda
August 28, 2024

Where it was heard

Special Magistrate Aug 28, 2024