15-9015
FIRE-24-0041 Property Address: 915 DOYLE ROAD, DELTONA, FL 32725 Parcel ID: 910609000010 Property Owner: TCB - DELTONA LLC 353 N CLARK SUITE 3625 CHICAGO, IL 60654-3477 Violation: City of Deltona Ordinance, : Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition, NFPA 13, 2019 Edition – Ch. 16.12.5.6 - Where a fire department connection services only a portion of a building, a sign shall be attached indicating the portions of the building served, NFPA 1 – Ch. 13.3.3.4.3.4 - As-built system installation drawings, hydraulic calculations, original acceptance test records, and device manufacturer’s data sheets shall be retained for the life of the system, Corrective Action: Please contact your fire sprinkler service provider to provide a hydraulic calculation plate for the retail plaza portion of the Publix building. Please provide signage for Fire Department Connection (FDC), directly in front of FDCs for Building 100, 200 & 300. Durable signage shall be a minimum of 6 inches in height, on contrasting background. Please ensure signage indicates "Bldg 100/200/300 FDC" on it. Fire Inspector Ajorie Bailey
- Committee
- Special Magistrate
- Introduced
- August 20, 2024
- On agenda
- August 28, 2024